Legionnaires’ Disease Outbreak in Murcia, Spain
Author Information
Author(s): García-Fulgueiras Ana, Navarro Carmen, Fenoll Daniel, García José, González-Diego Paulino, Jiménez-Buñuales Teresa, Rodriguez Miguel, Lopez Rosa, Pacheco Francisco, Ruiz Joaquín, Segovia Manuel, Baladrón Beatriz, Pelaz Carmen
Primary Institution: Regional Health Council of Murcia, Murcia, Spain
Hypothesis
The outbreak had its origin in environmental contamination from cooling towers or other installations capable of producing and dispersing large quantities of aerosols potentially contaminated by legionellae.
Conclusion
The cooling towers of a hospital located in the northeastern part of the city of Murcia were the origin of this community outbreak.
Supporting Evidence
- The outbreak was the world’s largest reported outbreak of Legionnaires’ disease with 449 confirmed cases.
- The case-fatality rate was 1.1% for confirmed cases.
- 95% of confirmed case-patients lived, worked, or visited in the northern districts in the 10 days before the outbreak began.
- Environmental samples from cooling towers matched the strains found in patients.
- Hospital admission was necessary for 64% of all reported case-patients.
Takeaway
A lot of people got sick from a disease called Legionnaires' disease because of contaminated water from cooling towers in a hospital.
Methodology
A case-control study matched 85 patients with two controls each to identify the outbreak source, along with an active surveillance system for pneumonia cases.
Potential Biases
Potential selection bias was evaluated but deemed unlikely since socioeconomic status and predisposing risk factors did not differ significantly between cases and controls.
Limitations
The study faced challenges such as a large number of potential sources of contamination and difficulties in isolating the Legionella strain initially.
Participant Demographics
74% of confirmed case-patients were men, with ages ranging from 19 to 91 years; 70% were over 50 years old.
Statistical Information
Confidence Interval
95% CI 4.2 to 45.9
Digital Object Identifier (DOI)
Want to read the original?
Access the complete publication on the publisher's website