AC Magnetometry Using Nano-ferrofluid Cladded Multimode Interferometric Fiber Optic Sensors for Power Grid Monitoring Applications
2024

Magnetic Fluid Fiber Optic Sensor for Power Grid Monitoring

publication 10 minutes Evidence: high

Author Information

Author(s): Karki Dolendra, Khanikar Tulika, Mullurkara Suraj V., Naeem Khurram, Hong Jun Young, Ohodnicki Paul

Primary Institution: University of Pittsburgh

Hypothesis

Can a magnetic fluid-cladded multimode interferometric fiber optic sensor effectively sense AC magnetic fields for power grid monitoring?

Conclusion

The sensor can detect AC magnetic fields up to 15 kHz with a maximum sensitivity of 9.91 mV/Gauss.

Supporting Evidence

  • The sensor achieved a magnetic field sensitivity of 240 mV/Gauss per dBm of transmitted power.
  • The response time of the sensor was optimized to approximately 1 ms.
  • The sensor was able to detect various current profiles and anomalies in power transmission lines.

Takeaway

This study shows that a special type of sensor using magnetic fluid can help monitor electricity in power lines by detecting magnetic fields.

Methodology

The sensor was optimized for high-frequency AC magnetic field sensing using a multimode interferometric structure with nano-ferrofluid as the cladding material.

Limitations

The sensor's response is influenced by the concentration of magnetic nanoparticles and may produce noise at lower currents.

Digital Object Identifier (DOI)

10.1021/acsanm.4c04912

Want to read the original?

Access the complete publication on the publisher's website

View Original Publication